Conductor:

Multiple-wire, round copper conductor class 2, DIN VDE 0281, IEC 60228

Insulation:

PVC insulation compound TI-1

Colour:

Green/Yellow, Blue, Black, Brown, Gray, Orange, Pink, Red, Violet, White, Green, Yellow or other colours

Cable Marking:

We are Provide 1 to 90 M. Sequential Marking on Cable

Flame propagation:

Flame retardant test as per IEC 60332-1

Cable features

  • High current carrying capacity
  • Excellent resistant to moisture, abrasion, grace, oil
  • Longer Flex Life
  • Excellent mechanical & electrical properties
  • harmonized acc. to European standards
  • Steam and boiling water resistant

Technical DataTable |Download Catalog

HO5V-R (300/500 V)
Nominal cross sectional area of conductor Nominal insulation thickness Mean overall diameter Max conductor resistance at 20°C Min insulation resistance at 70°C
Lower limit Upper limit
sqmm mm mm mm Ω / km MΩkm
0.50 0.60 2.00 2.40 36.00 0.014
0.75 0.60 2.20 2.60 24.50 0.012
1.00 0.60 2.30 2.80 18.10 0.011
HO7V-R (450/750 V)
Nominal cross sectional area of conductor Nominal insulation thickness Mean overall diameter Max conductor resistance at 20°C Min insulation resistance at 70°C
Lower limit Upper limit
sqmm mm mm mm Ω / km MΩkm
01.50 0.70 02.70 03.30 12.100 0.0100
02.50 0.80 03.30 04.00 07.410 0.0099
04.00 0.80 03.80 04.60 04.610 0.0082
06.00 0.80 04.30 05.20 03.080 0.0070
10.00 1.00 05.60 06.70 01.830 0.0067
16.00 1.00 06.40 07.80 01.150 0.0056
25.00 1.20 08.10 09.70 00.727 0.0053
35.00 1.20 09.00 10.90 00.524 0.0046
50.00 1.40 10.60 12.80 00.387 0.0046
70.00 1.40 12.10 14.60 00.268 0.0040
95.00 1.60 14.10 17.10 00.193 0.0039
120.00 1.60 15.60 18.80 00.153 0.0035
150.00 1.80 17.30 20.90 00.124 0.0035
185.00 2.00 19.30 23.30 00.100 0.0035
240.00 2.20 22.00 26.60 00.076 0.0034
300.00 2.40 24.50 29.60 00.061 0.0033
400.00 2.60 27.50 33.20 00.047 0.0031
500.00 2.80 30.50 26.90 00.037 0.0030
630.00 2.80 34.00 41.10 00.029 0.0027